In power engineering, winding factor provides a way to compare of the effectiveness of different designs of stators for alternators. "The winding factor is an operand in order to consider the effect of winding distribution and chording on the spatial distribution of the magnetic field in the air gap of synchronous and induction machines". Accordingly, the behaviour of synchronous and induction machines can be estimated. "The main torque production or electrical power generation can easily be related to the fundamental spatial and time harmonics, whereby the effect of other spatial and time harmonics is usually negligible. Indeed, the other spatial and time harmonics may contribute to the torque pulsation, noise, and vibration excitations" besides additional losses.

Last revised
Jun 16, 2026
Read time
≈ 4 min
Length
888 w
Citations
12
Source

In power engineering, winding factor k w {\displaystyle k_{w}} provides a way to compare of the effectiveness of different designs of stators for alternators. "The winding factor is an operand in order to consider the effect of winding distribution and chording on the spatial distribution of the magnetic field in the air gap of synchronous and induction machines"1. Accordingly, the behaviour of synchronous and induction machines can be estimated. "The main torque production or electrical power generation can easily be related to the fundamental spatial and time harmonics, whereby the effect of other spatial and time harmonics is usually negligible. Indeed, the other spatial and time harmonics may contribute to the torque pulsation, noise, and vibration excitations" 2 besides additional losses.

For most alternators, the stator acts as the armature.

Practical alternators have a short-pitched and distributed windings to reduce harmonics and maintain constant torque. Also, either the stator or rotor may be slightly skewed from the rotor's axis to reduce torque ripple. The armature winding of each phase may be distributed in a number of slots for certain number of pole pairs. Since the EMF induced in different slots are not in phase, their phasor sum is less than their numerical sum.3 This reduction factor is called distribution factor k d {\displaystyle k_{d}} . The other factors that can reduce the winding factor are pitch factor k p {\displaystyle k_{p}} and skew factor k s {\displaystyle k_{s}} .

Pitch

In alternator design, pitch means angle. The shaft makes a complete rotation in 360 degrees, and is called mechanical degrees. However, the current in a conductors makes a complete cycle in 360 electrical degrees. Electrical degrees and mechanical degrees are related as follows:

electrical degrees = P 2 mechanical degrees {\displaystyle {\text{electrical degrees}}={\frac {P}{2}}\cdot {\text{mechanical degrees}}}

where P {\displaystyle P} is the number of poles 4. Note that in many considerations such as the closed-form distribution factor, p {\displaystyle p} refers to the number of pole pairs, i.e., p = 1 2 P {\displaystyle p={\frac {1}{2}}\cdot P} .

No matter how many poles, each pole always spans exactly 180 electrical degrees, and it is called pole pitch. Coil pitch is the number of electrical degrees spanned by the coil.3

Short pitch factor

A full-pitched coil is 180 electrical degrees, meaning it spans the entire pole. A short-pitched coil is less than 180 electrical degrees, meaning it does not spans the entire pole. The amount the coil is short-pitched is given by the variable a {\displaystyle a} in electrical degrees:

a = pole pitch coil pitch {\displaystyle a={\text{pole pitch}}-{\text{coil pitch}}} , and the pitch factor is:

k p = cos ( a 2 ) {\displaystyle k_{p}=\cos({\frac {a}{2}})} .

A short pitched coil is also called chorded, in reference to the chord of a circle.3

Calculating winding factor

The winding factor is defined by the product of the distribution and pitch factors
k w = k d k p {\displaystyle k_{w}=k_{d}k_{p}} 516

while the coupling factor can be calculated as
k w = k d k p k s {\displaystyle k_{w}=k_{d}k_{p}k_{s}} 178

where
k d {\displaystyle k_{d}} is the distribution factor.
k p {\displaystyle k_{p}} is the pitch factor.
k s {\displaystyle k_{s}} is the skew factor resulting from skewing between the stator and rotor.

Example

For a 3-phase 6 slot 4 pole non-overlapping winding alternator:
coil pitch = 2 π 6 = π 3 ( mech ) = 2 π 3 ( elec ) {\displaystyle {\text{coil pitch}}={\frac {2\pi }{6}}={\frac {\pi }{3}}({\text{mech}})={\frac {2\pi }{3}}({\text{elec}})}
pole pitch = 2 π 4 = π 2 ( mech ) = π ( elec ) {\displaystyle {\text{pole pitch}}={\frac {2\pi }{4}}={\frac {\pi }{2}}({\text{mech}})=\pi ({\text{elec}})}

Most of 3-phase motors have winding factor values between 0.85 and 0.95.

The winding factor (along with some other factors like winding skew) can help to improve the harmonic content in the generated EMF of the machine.

References

References

  1. Raziee, S. M.; Misir, O.; Ponick, B. (6 June 2017). "Winding Function Approach for Winding Analysis". IEEE Transactions on Magnetics. 53 (10): 1–9. Bibcode:2017ITM....53A2570R. doi:10.1109/TMAG.2017.2712570.
  2. Raziee, S. M. (June 2026). "Performance and NVH Analysis of Comparable Synchronous Machines With Single- and Double-Layer Fractional-Slot Distributed Windings". IEEE Transactions on Industrial Electronics. 73 (6): 8114–8124. Bibcode:2026ITIE...73.8114R. doi:10.1109/TIE.2025.3613631.
  3. Suad Ibrahim Shahl. "Introduction to AC Machines" (PDF). p. 7. Retrieved August 3, 2022.
  4. "Armature Winding". Circuit Globe. 5 January 2016. Retrieved July 29, 2022.
  5. Binder, A. "Verteilte Wicklung - Zahnspulenwicklung" (PDF). Technische Uinversität Darmstadt.
  6. "IEC 411-38-39, Electropedia: winding factor". Electropedia. International Electrotechnical Commission (IEC). 1996.
  7. Müller, G.; Ponick, B. (2009). Theorie elektrischer Maschinen. Weinheim: Wiley-VCH. ISBN 978-3-527-40526-8.
  8. Mustafa Al-Refai (2018). "Synchronous generator" (PDF). Electrical and Communications Consulting Office (ECCO). p. 20. Retrieved August 6, 2022.